APCS of the turbo unit No. 4 of Jezkazgan CHPP
The APCS implementation is executed due to replacement of turbo unit No. 4 of R-25-8.8 / 2.9 type with turbo unit of T-50 / 60-8.8 type.
The APCS of turbo unit No. 4 is designed for process automation of electrical and thermal energy production in all operating modes and provides:
- Monitoring and automation control of the main and auxiliary technological equipment of the turbo unit;
- Technological protection of the turbo unit;
- Control of the main parameters of the electrical equipment.
3.1. The APCS of the turbo unit No. 4 includes the following technological equipment:
-
Turbine plant;
-
Generator of TSFP 63-2MUZ type.
3.2. The structure of the turbine plant includes the following components:
- T-50 / 60-8,8 / 0.12 steam turbine with heat extraction of steam (the main parameters and characteristics of the turbine are given in Table 3.1);
- Auxiliary equipment and pipelines;
- Heating unit with a horizontal delivery water heater.
3.3. Turbo generator of TSFP-63-2MUZ type is three-phased, synchronous, with air-cooling, general purpose (the main generator parameters are given in Table 3.2).
3.4. The automation object is located in the area with the following outside temperatures:
- Average maximum temperature of the hottest month: +29.8 °C;
- Average temperature of the coldest month: -15.2 °C.
Table 3.1.
Parameter name |
Unit of measure |
Parameter value |
Nominal electric capacity |
MW |
55,7 |
Maximum electric capacity |
MW |
66,6 |
Nominal rotation speed of rotor |
RPM |
3000 |
Nominal steam pressure before the isolation valve (abs.) |
kgf/sm2 |
90 |
Nominal temperature before the isolation valve |
°C |
535 |
Nominal steam pressure in the controlled production extraction (abs.) |
kgf/cm2 |
1,2 |
Nominal temperature in the controlled production extraction (abs.) |
°C |
104 |
Nominal consumption of the steam in the heating extraction at nominal steam parameters in the extraction |
t/h |
150 |
Nominal thermal load of the controlled heating steam extraction |
Gcal/h |
79 |
Maximum operating absolute pressure of the steam in the controlling stage chamber (behind the stage) |
kg/sm2 |
462 |
Table 3.2.
Parameter name |
Unit of measure |
Parameter value |
Full capacity |
kVA |
78750 |
Active capacity |
kW |
63000 |
Voltage |
V |
10500/6300 |
Stator current |
A |
4330/7217 |
Rotor current (calculated) |
A |
800 |
Rotor voltage (calculated) |
V |
325 |
Power factor |
|
0.8 |
Efficiency |
% |
98.3 |
Static overload capacity, no less than |
|
0.45 |
Lead count of stator winding |
|
6 |
Current frequency |
Hz |
50 |
Rotation speed of the rotor |
RPM |
3000 |
Critical rotation speeds of the rotor
|
RPM
|
1400
3550
|
Minimum / Maximum temperature of cooling water |
°C |
12/32 |
Nominal water consumption of the air coolers |
m3/h |
300 |
3.5. The number of shutoff and control valves:
- gates, shutoff valves – 138;
- control valves – 22.
3.6. The number of auxiliary devices: 21, including:
- for 0.4 kV voltage – 20;
- for 220 V voltage – 1.
Total electric drives: 180.
3.6. Preliminary number of the input parametric DCS signals (without signals via shutoff & control valves and auxiliary devices):
-
Temperature measurements: 188;
- Analog parametric measurements: 181;
- Discrete parametric measurements: 86.
Total parametric signals: 455.
3.7. Local subsystems integrated into the APCS: electro-hydraulic system of automatic control, “Vibrobit-300” automated control system of vibration, relay protection & automatic equipment of “EKRA” generator.